The NA2XSBY cable is a medium-voltage, single-core power cable featuring:
Aluminium conductor
XLPE insulation (cross-linked polyethylene)
Copper tape screen
Aluminium tape armor (ATA)
PVC outer sheath
It is designed for mechanical protection and power transmission in medium-voltage networks.
Used in power distribution networks, especially where:
Mechanical protection is required (e.g., underground installations)
Lighter weight than copper is desired
Suitable for:
Industrial facilities
Substations
Power plants
Outdoor/underground cable trenches
Direct buried
Ducts
Cable trays
Not intended for applications with high tensile stress (e.g., overhead)
Standard | Description |
---|---|
IEC 60502-2 | Power cables with extruded insulation for rated voltages 3.6/6 kV up to 30/33 kV |
IEC 60228 | Conductors (Class 2, stranded aluminium) |
IEC 60332-1 | Flame retardance |
IEC 60754 | Halogen content (PVC is not halogen-free) |
IEC 61034 | Smoke density |
Component | Specification |
---|---|
Conductor | Aluminium, stranded (Class 2 per IEC 60228) |
Conductor Screen | Extruded semi-conductive layer |
Insulation | XLPE (cross-linked polyethylene) |
Insulation Screen | Semi-conductive layer over XLPE |
Metallic Screen | Copper tape (helically applied or longitudinal) |
Separator Tape | Non-metallic (optional) |
Armor | Aluminium tape armor (helically applied) |
Outer Sheath | PVC (black, UV resistant, flame retardant) |
Parameter | Value |
---|---|
Rated Voltage (U0/U) | 3.6/6 to 18/30 kV |
Max Operating Temp. | 90°C |
Short-Circuit Temp. | 250°C (max 5 s) |
Min Installation Temp. | 0°C (recommended ≥ 5°C) |
Min Bending Radius | ≥ 15 × outer diameter |
Flame Retardant | IEC 60332-1 |
UV Resistance | Yes (black sheath) |
EMC Compatibility | Copper screen provides shielding |
Halogen Content | Not halogen-free (PVC sheath) |
Rated Voltage | XLPE Thickness |
---|---|
3.6/6 kV | 3.4 mm |
6/10 kV | 4.5 mm |
8.7/15 kV | 5.5 mm |
12/20 kV | 6.5 mm |
18/30 kV | 8.0 mm |
Feature | Specification |
---|---|
Cable Type | NA2XSBY |
Core | 1 core |
Conductor | Aluminium (Class 2) |
Insulation | XLPE |
Screen | Copper tape |
Armor | Aluminium Tape Armor (ATA) |
Outer Sheath | PVC (black) |
Voltage Rating | 3.6/6 to 18/30 kV |
Standard | IEC 60502-2 |
Lower cost and weight compared to copper conductor cables
Good thermal and electrical performance with XLPE
Suitable for direct burial (with ATA)
Improved mechanical protection due to aluminium tape armor
Resistant to UV and common environmental agents
Specification