NA2XSY is a single-core, medium-voltage power cable constructed with:
Aluminium conductor
XLPE insulation
Copper tape screen
Aluminium wire armor (AWA)
PVC outer sheath
This cable is designed for fixed installations where non-magnetic armor is required due to alternating current (AC) use, typically in single-core applications.
Medium voltage (MV) power distribution
Indoor and outdoor fixed installations
Power transmission in utility substations, industrial plants, and commercial buildings
Direct burial in the ground
Cable trays and ducts
Suitable for wet or dry locations
Environments requiring mechanical protection
Aluminium wire armor (AWA) avoids magnetic interference in single-core AC systems, preventing eddy current losses and overheating.
Excellent performance in harsh environments.
Standard | Title |
---|---|
IEC 60502-2 | Power cables with extruded insulation and their accessories for rated voltages from 3.6/6 kV up to 30/52 kV |
IEC 60228 | Conductors of insulated cables |
IEC 60332-1 | Flame propagation for a single cable |
IEC 61034 | Smoke density measurement during combustion |
IEC 60754 | Halogen acid gas emission testing |
Component | Material / Feature |
---|---|
Conductor | Stranded aluminium (Class 2 as per IEC 60228) |
Conductor Screen | Extruded semi-conductive layer |
Insulation | Cross-linked polyethylene (XLPE) |
Insulation Screen | Extruded semi-conductive layer |
Metallic Screen | Helically applied copper tape |
Armoring | Aluminium wire armor (AWA) for mechanical protection and AC compatibility |
Outer Sheath | PVC, black, UV and flame-resistant |
Parameter | Value |
---|---|
Rated Voltage (U0/U) | 3.6/6 kV up to 18/30 kV |
Max. Operating Temp. | 90°C |
Max. Short-circuit Temp. | 250°C (for 5 seconds) |
Min. Bending Radius | 15 × overall diameter |
Installation Temp. | ≥ 0°C |
Flame Retardant | Yes (IEC 60332-1 compliant) |
Rated Voltage | XLPE Thickness |
---|---|
3.6/6 kV | 3.4 mm |
6/10 kV | 4.5 mm |
8.7/15 kV | 5.5 mm |
12/20 kV | 6.5 mm |
18/30 kV | 8.0 mm |
Property | Specification |
---|---|
Cable Type | NA2XSY |
Conductor | Aluminium |
Insulation | XLPE |
Screen | Copper tape |
Armor | Aluminium wire (AWA) |
Sheath | PVC |
Voltage Rating | 3.6-30 kV |
Core Configuration | 1 core |
Standard | IEC 60502-2 |
Lightweight and corrosion-resistant aluminium conductor
Non-magnetic armor ideal for AC single-core installations
Excellent dielectric strength and thermal performance with XLPE
Reliable mechanical protection through AWA
Durable PVC sheath for UV, abrasion, and flame resistance
Specification